Hot Water Systems (HWS) Laboratory

The HWS Laboratory is a facility at the Florida Solar Energy Center (FSEC) - UCF grounds in Cocoa, FL used to test a variety of hot water systems simultaneously side by side. The 160 Sq.ft. metal roof building currently houses seven hot water systems including electric, solar thermal, natural gas and tankless systems. The project is part of the Building America program funded by DOE. www.baihp.org/hwslab

The HWS Lab houses a 50-gallon electric tank, differential controlled flat plate collector system w/80 gallon electric assisted tank, 40-gallon Integrated collector system(ICS) backed-up by a 50-gallon electic, PV pumped flat plate collector system w/80 gallon electric assisted tank,a conventional 40-gallon natural gas tank,a natural gas tankless system, and an electric heat pump water heater. All auxiliary heating elements are rated to 4500W. Natural gas tank is rated at 38,000 Btu/hr and the tankless can provide up to 190,000 Btu/hr. Details on the measurements and calculations are briefly covered in a calculations procedures link.


HWS Laboratory Event Log - Phase 1 (Mar2009 - May 2010)

HWS Laboratory Event Log - Phase 2 (July 2010)

HWS Laboratory Event Log - Phase 3 (FEB 2012)

Caution: Data being collected are preliminary and cannot be used to characterize relative performance without understanding changing experimental conditions. Valid data have been collected for the systems in final configuration since 10 March, 2009. Data on system performance prior to insulation of piping can be seen from 3 February - 2 March, 2009.

Feb 02 2012, 00:15 -To- Feb 03 2012, 00:00 EST

Electricity Usage

kWh

ELECTRIC TANK 50 GAL 9.4
HYBRID HPWH/80 GAL DIFF. FLAT PLATE 0.0
ICS WITH HEAT PUMP WATER HEATER 1.9
STD ELECTRIC 50 GAL & CAP-WRAP INSULATION 8.8

Parasitic Energy

kWh

DIFFERENTIAL CONTROLLER/PUMP 0.072
SOLAR/GAS HYBRID TANKLESS CONTROLS 0.169
GAS TANKLESS Controls 0.000

Natural Gas Usage

cu. ft.

40 GAL NAT. GAS HEATER 47.7
SOLAR/GAS NAT. GAS TANKLESS HEATER 5.8
NG TANKLESS COND. HEATER 31.0

Energy Output

BTU's

ELECTRIC TANK 50 GAL 26023.0
HYBRID HPWH/80 GAL DIFF. FLAT PLATE 0.0
ICS WITH HEAT PUMP WATER HEATER 24500.0
80 GAL PV PUMP SOLAR/NG HYBRID 24459.0
50 GAL NAT. GAS TANK 28696.0
NG TANKLESS COND. HEATER 26130.0
STD ELECTRIC 50 GAL & CAP-WRAP INSULATION 27115.0

Weather Conditions

Integrated/AVG.

Min/Max
SOLAR INSOL. @ 22 deg (Whrs/Sq.m) 5549.7 -8.9/ 1167.8
Outdoor Temp (deg F) 66.6 56.3/ 80.3
Indoor Shed Space Temp (deg F) 72.4 63.1/ 85.2

Daily Efficiencies (COP)

* parasitic energy included

ELECTRIC TANK 50GAL 0.81
HYBRID HPWH/80 GAL DIFF. FLAT PLATE 0.00
ICS WITH HEAT PUMP WATER HEATER 3.78
80 GAL PV PUMP SOLAR/NG HYBRID 4.13
40 GAL NAT. GAS TANK 0.59
NG TANKLESS COND. HEATER * 0.81
STD ELECTRIC 50 GAL & CAP-WRAP INSULATION 0.91

Total Daily Gallons

gal.

ELECTRIC TANK 50 GAL 62.9
HYBRID HPWH/80 GAL DIFF. FLAT PLATE 1.0
ICS WITH HEAT PUMP WATER HEATER 62.4
80 GAL PV PUMP SOLAR/NG HYBRID 60.2
40 GAL NAT. GAS TANK 62.0
NG TANKLESS COND. HEATER 65.6
STD ELECTRIC 50 GAL & CAP-WRAP INSULATION 62.9

Draw-weighted Inlet Tempratures

deg. F

ELECTRIC TANK 50 GAL 69.1
HYBRID HPWH/80 GAL DIFF. FLAT PLATE 71.6
ICS WITH HEAT PUMP WATER HEATER 90.3
80 GAL PV PUMP SOLAR/NG HYBRID 69.1
NATURAL GAS 40 GAL 69.3
NG TANKLESS COND. HEATER 69.6
STD ELECTRIC 50 GAL & CAP-WRAP INSULATION 69.0

Draw-weighted Outlet Tempratures

deg. F

ELECTRIC TANK 50 GAL 118.3
HYBRID HPWH/80 GAL DIFF. FLAT PLATE 83.1
ICS WITH HEAT PUMP WATER HEATER 116.9
80 GAL PV PUMP SOLAR/NG HYBRID 113.7
NATURAL GAS 40 GAL 124.2
NG TANKLESS COND. HEATER 115.6
STD ELECTRIC 50 GAL & CAP-WRAP INSULATION 120.0